We are one of the finest Flame Arrester
Manufacturers in India. A
flame arrester is a safety device whose principal purpose is to prevent a flame
entering or leaving a pipe or vessel or to prevent it travelling further down a
pipe. In many cases it is used in conjunction with other components to create a
safety system. A flame arrester uses an element with small
apertures which allows gas or vapour to pass. If the apertures are smaller than
the maximum experimental safe gap (MESG) for the gas or vapour then a flame
cannot pass through the arrester, and is subsequently contained or
extinguished.
A flame arrester functions by forcing a flame front through channels too narrow
to permit the continuance of a flame. These passages can be regular, like wire mesh or a sheet metal
plate with punched holes, or irregular, such as those in random
packing.
There are different types
of flame arrester, each of which is designed to handle certain conditions. It
is essential that the flame arrester is correctly specified to ensure that a
flame is extinguished (or properly contained) and that an explosion is
prevented from propagating through the equipment. The first step in specifying
a flame arrester is to determine the location of the potential ignition source.
Only when this has been established can one start to understand what is to be
protected and how.
Applications:
Ø Vapour Recovery Lines,
Ø Combustible gas lines of
low-high calorific value gas,
Ø Fuel gas lines,
Ø Purge lines,
Ø Compressors,
Ø Waste treatment plants,
Ø Flare systems,
Ø
Ø Incinerators,
Ø Biogas lines,
Ø Storage tanks,
Ø Engines,
Ø Chemical, Petrochemical
Plants,
Ø Gas Trains,
Ø Pulp and Paper,
Ø Food and Beverage,
Ø Process Industry,
Ø Adhesives, Resins,
Paints,
Ø Automotive etc.
FLAME ARRESTERS ARE SUBCATEGORIZED
AS:
1.
DEFLAGRATION ARRESTORS
The
deflagration arrestors are generally used with group I gases. These gases do
not have the detonation characteristics.
2.
DETONATION ARRESTER
If
the gases belong to II A, IIB and IIC group with high detonation
characteristics and flame front travelling at speed exceeding Mach 1
(supersonic) then the detonation arresters are advised. Detonation
arrestors are also advised in pipelines with high working temperature of the
medium.
3.
IN LINE FLAME ARRESTOR
These flame arrestors are used in the pipe line and
manufactured for flame deflagration and Detonation.
4.
END OF LINE FLAME ARRESTORS
They
are normally used on the storage tanks or for venting the combustible gases
into the atmosphere. The protection of these flame arrestors is generally for
Deflagration only.
These
flame arrestors are used in the pipe line and manufactured for flame
deflagration and Detonation.
MATERIAL OF CONSTRUCTION:
HOUSING:
Low Copper Aluminium, Cast iron, Stainless Steel, - Other materials and
coatings available on request.
FLAME
ELEMENT: SS316, SS304, Aluminium, Copper.
SIZES:
Sizes
are available from ¼" to 12" (6mm to 300 mm) Other/Higher sizes
available on request
PRESSURE
RATING:
Standard
5- 10 bar. High-pressure ratings available on request.